Dival 600 is one of the direct-operated gas pressure regulators controlled by a diaphragm and contrasting regulated spring action by Pietro Fiorentini. Mainly used for medium and low pressure natural gas distribution networks, it can be used with previously filtered gaseous fluids. According to the European Standard EN 334, it is classified as Fail Open.
P inlet (bar) | |||||
---|---|---|---|---|---|
m3/h | 0,3 | 1 | 2 | 4 | |
P outlet (mbar) |
21 | 330 | 670 | 1100 | 1208 |
100 | 300 | 680 | 1100 | 1400 | |
300 | - | 620 | 1100 | 1350 | |
1000 | - | - | 840 | 1500 |
MODEL | DIAMETER | P (outlet range) |
---|---|---|
DIVAL 600 BP | DN 40 | 12 - 120 mbar |
DIVAL 600 MP | DN 40 | 90 - 340 mbar |
DIVAL 600 TR | DN 40 | 0,3 - 4,2 bar |
P inlet (bar) | |||||
---|---|---|---|---|---|
m3/h | 0,3 | 1 | 2 | 4 | |
P outlet (mbar) |
21 | 389 | 798 | 1258 | 1460 |
100 | 320 | 700 | 1100 | 1800 | |
300 | - | 650 | 1300 | 2100 | |
1000 | - | - | 1200 | 2200 |
MODEL | DIAMETER |
P (outlet range) |
---|---|---|
DIVAL 600 BP | DN 50 | 12 - 120 mbar |
DIVAL 600 MP | DN 50 | 90 - 340 mbar |
DIVAL 600 TR | DN 50 | 0,3 - 4,2 bar |